Calculate exact NEC wire gauge, real-time voltage drop, and breaker sizing for EV chargers, solar arrays, RVs, and home subpanels.
Standard North American allowable ampacities for insulated Copper (Cu) and Aluminum (Al) conductors rated at 60°C (NM-B Romex / UF-B) and 75°C (THHN / THWN-2 / XHHW), including NEC 240.4(D) small conductor breaker limits.
| Wire Gauge | Copper 60°C (NM-B) | Copper 75°C (THHN) | Aluminum 75°C | Max Breaker (Cu) | Typical North American Application |
|---|---|---|---|---|---|
| 14 AWG | 15 A | 20 A* | — | 15 Amp | Lighting circuits, bedroom outlets |
| 12 AWG | 20 A | 25 A* | 20 A* | 20 Amp | Kitchen, bathroom, garage 20A receptacles |
| 10 AWG | 30 A | 35 A* | 30 A* | 30 Amp | Electric clothes dryers, 30A RV, water heaters |
| 8 AWG | 40 A | 50 A | 40 A | 40–50 Amp | 32A–40A Level 2 EV chargers, electric ranges |
| 6 AWG | 55 A | 65 A | 50 A | 50–60 Amp | 48A EV chargers (THHN), 50A RV pedestals, hot tubs |
| 4 AWG | 70 A | 85 A | 65 A | 70–80 Amp | 60A–80A subpanels, long-run 48A EV chargers |
| 3 AWG | 85 A | 100 A | 75 A | 100 Amp | 100A residential garage subpanel (Copper) |
| 2 AWG | 95 A | 115 A | 90 A | 90–115 Amp | 90A–100A feeder subpanels (Al MHF / SER) |
| 1 AWG | 110 A | 130 A | 100 A | 125 Amp | 100A Aluminum feeder / 125A Copper subpanel |
| 1/0 AWG | 125 A | 150 A | 120 A | 150 Amp | 125A–150A service entrance & heavy feeders |
| 2/0 AWG | 145 A | 175 A | 135 A | 175–200 Amp | 200A residential service entrance (Copper NEC 310.12) |
| 3/0 AWG | 165 A | 200 A | 155 A | 200 Amp | 200A commercial continuous main feeder (Copper) |
| 4/0 AWG | 195 A | 230 A | 180 A | 200–225 Amp | 200A residential service entrance (Aluminum) |
*Per NEC 240.4(D), overcurrent protection shall not exceed 15A for 14 AWG, 20A for 12 AWG, and 30A for 10 AWG copper conductors in standard branch circuits.